Gas Detection in Food & Beverage: CO2, Ammonia Refrigeration & Fermentation

Introduction

Food and beverage plants look harmless from the outside, yet they routinely run some of the most dangerous atmospheres in industry. Carbon dioxide (CO2) from fermentation and dry-ice handling, ammonia (NH3) from large refrigeration systems, and oxygen depletion inside silos, cellars and enclosed processing rooms can injure or kill a worker within minutes. A proper food industry gas detection programme therefore has to combine fixed area monitoring, portable entry instruments and central alarm handling — all certified for the zones where food, dust and cold meet.

This article explains where the gas hazards sit in a typical food plant, which gases matter most, how fixed and portable detection are selected, and how a control architecture should be specified for EAC, ATEX and IECEx markets.

Where Gas Hazards Arise in a Food Plant

Fermentation, Brewing and Carbonation

Beer, wine, yeast cultures, bread and carbonated drinks all produce or release CO2. Because CO2 is about 1.5 times heavier than air, it collects at floor level, in cellars, around open fermenters and inside tank bottoms. A poorly ventilated fermentation hall can exceed the 5,000 ppm long-term exposure limit within minutes, and levels above 5% rapidly impair breathing. Ethylene (C2H4) and, in anaerobic digesters, trace hydrogen sulfide (H2S) can also appear in waste and treatment areas.

Ammonia (NH3) Refrigeration

Large cold stores, dairies, meat processing and fruit-ripening rooms in Russia and the Middle East commonly use ammonia as the refrigerant. NH3 is toxic, corrosive to copper alloys and — at high concentration — flammable. A single flange or seal leak in a compressor room can fill the space quickly. Detection must be placed near potential leak points and at low level for the heavier-than-air refrigerant charge.

Silos, Packaging and Fuel Forklifts

Grain and powder silos present oxygen-deficiency and, in dusty product, an explosible dust atmosphere. Meanwhile, propane- or LPG-powered forklifts and combustion boilers add carbon monoxide (CO) risk in loading bays and utility rooms.

Typical Exposure Reference Levels

The table below summarises commonly referenced occupational exposure ranges. They are reference values, not a substitute for the limit set by the buyer’s national regulation, and they must be confirmed against the applicable standard for each site.

Gas Common health concern (reference) Typical monitoring location
Carbon dioxide (CO2) Excess ventilation / hypercapnia above ~5,000–10,000 ppm; dangerous at >5% Fermentation halls, cellars, bottling, dry-ice areas
Ammonia (NH3) Irritant to eyes and respiratory tract; toxic above low ppm Compressor rooms, cold-storage valve stations, accumulators
Oxygen (O2) Enrichment >23.5% or deficiency <19.5% is hazardous Silos, tanks, enclosed fermentation vessels
Carbon monoxide (CO) Odourless toxic gas from combustion / LPG lift trucks Boiler rooms, loading bays, forklift charging areas
Combustible (LEL) Flammable atmosphere around refrigerants, solvents, dust Solvent areas, dust extraction, fuel storage

Fixed vs. Portable Detection in a Food Plant

Fixed Area Monitoring

Continuous areas such as ammonia compressor rooms, fermentation halls and bottle-filling zones need fixed detectors that never sleep. A fixed instrument continuously measures and drives ventilation, alarms and an emergency stop. The HD9300 fixed gas detector with LCD display uses an Ex d IIC T6 Gb enclosure, operates from -40 to +70 °C and outputs 4-20 mA, RS485 or MBUS to a DCS or PLC, with dual relays and IR remote calibration — well suited to cold-store and process areas. Where dust is present, the HD9100 fixed dust and gas alarm adds dust monitoring on a 2/3/4-wire loop.

Portable Entry and Personal Protection

Every time someone enters a silo, tank, cellar or confined space, a handheld instrument must be used to pre-test the atmosphere and to alarm continuously inside it. The HD620 four-in-one portable gas detector measures H2S, CO, O2 and LEL in one pumped instrument, is rated Ex ia IIC T4 Ga, IP65, runs roughly 20 hours on a 5,000 mAh battery on a 2.4-inch colour screen, and combines audible, visual and vibration alarms with voice prompts. For single-gas personal monitoring (for example NH3 or CO), the HD600 single-gas portable detector provides a compact daily-use solution.

Central Control and Alarm Logic

Fixed detectors should feed a central controller so that operators see every channel on one panel and can interlock ventilation, sirens and site alarm systems. The HD6000 gas alarm controller scales from 2 to 128 channels on 2/3/4-wire loops with an LCD or colour display, covering a multi-line dairy or beverage plant from one cabinet. For a single compressor room or loading bay, the HD6100 single-point wall-mounted controller is an all-in-one local panel.

For buyers in Russia and the Eurasian Union, equipment should be selected against EAC (TR CU 012/2011) requirements; for the Middle East and international projects, ATEX and IECEx certification and EN 60079 series conformity are the usual specification baseline.

Hangwei Food & Beverage Detection Solutions

Henan Hangwei Sensing Technology Co., Ltd. manufactures fixed and portable gas detection with more than 20 years of experience, 20 patents and 10 production lines, supporting OEM/ODM and custom detector-and-controller packages.

  • Fixed NH3 / CO2 / LEL monitoring in compressor rooms, fermentation and filling halls (HD9300; HD9100 for dust).
  • Confined-space and personal monitoring with the HD620 four-gas and HD600 single-gas portables.
  • Central alarm logic from 2 to 128 channels (HD6000) or single-point wall panels (HD6100).
  • Custom sensor configurations for special gases or ranges — see custom gas sensor solutions.

FAQ

Why is CO2 so dangerous in a fermentation hall?

CO2 is heavier than air and accumulates at low level and in cellars, displacing oxygen. Elevated concentrations cause rapid shortness of breath and confusion, so continuous CO2 detection plus oxygen monitoring is required before entry.

Which gas detector is used for ammonia refrigeration?

Ammonia is measured with electrochemical NH3 sensors, typically in fixed detectors installed in compressor rooms, near valve stations and below possible leak points, tied into ventilation interlocks and a central controller.

Do food plants need explosion-proof detectors?

Where flammable refrigerant, solvent vapour or explosible dust can occur, yes — equipment must carry the appropriate Ex marking (Ex d or Ex ia) and certification such as EAC, ATEX or IECEx for the intended zone.

Should I choose a pumped or diffusion portable detector?

Pumped instruments (such as the HD620 pump version) let you draw a sample from a distance before entering, which is ideal for confined-space pre-entry testing. Diffusion instruments are lighter and suit continuous personal wrist- or belt-worn monitoring.

How many detection channels does a bottling plant need?

It depends on the number of monitored rooms and leak sources. Small plants may use one single-point controller; multi-line facilities commonly require a controller covering tens of channels, scalable to 128 on the HD6000.

Get Expert Guidance

Specifying food & beverage gas detection means matching sensor, housing, wiring and certification to the room — compressor hall, fermentation cellar, silo or loading bay. Hangwei Sensors designs and manufactures fixed detectors, portables and controllers as one integrated package, and supports OEM/ODM and custom projects for buyers in Russia, the Middle East and worldwide.

Talk to our engineering team: email [hw@hangweisensors.com](mailto:hw@hangweisensors.com), call +86 371 6667 0886, or use the contact page. Browse the range: HD9300 fixed gas detector, HD620 four-in-one portable, and the HD6000 multi-channel controller.

Sources & References

[1] Hangwei Sensors — HD9300 Fixed Gas Detector product page — https://www.hangweisensors.com/product/hd9300-3-wire-system-4-wire-system-fixed-gas-detector-with-lcd-display/

[2] Hangwei Sensors — HD620 Four-In-One Portable Gas Detector (Pump) product page — https://www.hangweisensors.com/product/portable-gas-detector-hd620-four-in-one-pump/

[3] Hangwei Sensors — HD6000 Gas Alarm Controller (2–128 channels) product page — https://www.hangweisensors.com/product/4-parallel-wire-128-channels-fixed-gas-alarm-controller-hd6000-color-lcd/

[4] Hangwei Sensors — HD9100 Fixed Dust & Gas Alarm product page — https://www.hangweisensors.com/product/fixed-dust-gas-alarm-hd9100-2-3-4-wires-system-with-number-display/

[5] Hangwei Sensors — Custom Gas Sensor & Detector Solutions — https://www.hangweisensors.com/custom-gas-sensor/

[6] Hangwei Sensors — About Us — https://www.hangweisensors.com/about-us/

Scroll to Top